Heat Shrinkable Cable Termination

For connection of Cable to Switchgear Terminal, Transformer Terminal, Poles etc. termination kits are required. The Heat Shrinkable Termination kits can be Indoor or Outdoor based on actual application. It can also be single core or 3 core / 3.5 core based on cable configuration. Termination can be for XLPE & PILC Cable and can be used in extreme hazardous atmosphere conditions.

Features

There are wide range of cable jointing systems available today, which can be classified by the way they are applied such as taped type, pre-moulded / push-on / slip-on type, cold application type and heat shrinkable type. The selection criterion for an appropriate type of cable jointing system by the user should be dependent on the site conditions, operating parameters, voltage applications and cable types.

A.C. Voltage withstandDry: A.C. 35 kV / I min. Wet: A.C. 35 kV/ I min.
DC Voltage withstand 48 kV for 30 min.
Impulse Voltage withstand 75 kV 10 + VE & 10 - VE Shots

Specifications

Test Item of Heat Shrinkable Termination as per IEC-60502-4 / IS:13573

Testing Items U o/U6.35/11 kV12.7/22 kV19/33 kV
A.C. withstand test29kV, 5min, no flashover 58kV, 5min, no flashover 86kV, 5min, no flashover
Partial discharge test11kV < 10pc (Max.) 22kV < 10pc (Max.) 33kV < 10pc (Max.)
Thermal Cycles (63 cycles)under 95-100oC 16kV under 95-100o C 32kV under 95-100o C 48kV
Impulse voltage test75kV no flashover 125kV no flashover 170kV no flashover
A.C. with stand test16kV, 15 min, no flashover 32kV, 15 min, no flashover48kV, 15 min, no flashover
Humidity test (Indoor)No flashover, tracking erosion or mechanical damage occured at 300hrs, 8kV No flashover, tracking erosion or mechanical damage occured at 300hrs, 16kVNo flashover, tracking erosion or mechanical damage occured at 300hrs, 24kV
Salt Fog test (Outdoor)No flashover, tracking erosion or mechanical damage occured at 1000hrs, 8kV no flashover, tracking No flashover, tracking erosion or mechanical damage occured at 1000hrs, 16kV no flashover, trackingNo flashover, tracking erosion or mechanical damage occured at 1000hrs, 24kV no flashover, tracking